Apr 7, 2026
Permit/Opening
19 - adequate turnover rate
13-190(a): Pool equipment shall operate to obtain the minimum required number of 1 turnover every 6 hours. Observed turnover rate of 7.4 hours.
1550 BRIANWOOD RD DECATUR, GA 30033
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-190(a): Pool equipment shall operate to obtain the minimum required number of 1 turnover every 6 hours. Observed turnover rate of 7.4 hours.
Routine
13-190(a): Observed flowrate at 115 gpm. Equipment shall be operated to obtain a minimum turnover rate of 136 gpm for a 48891 gallon pool.
Permit/Opening
13-190(a): Observed flowrate at 115 gpm. Equipment shall be operated to obtain a minimum turnover rate of 136 gpm for a 48891 gallon pool.
Routine
13-198(b): standing water was observed in the equipment room. Advised to make sure drain was not clogged.
Routine
Pool must have a lined trash receptacle. No trash can was observed.
Permit/Opening
Observed flow meter reading at 120gpm. Turnover rate must be a minimum 135gpm.
Permit/Opening
13-202(g) Emergency phone not working at time of inspection. An operable, hard-wired, weatherproof telephone with 911 capability shall be installed in a conspicuous location and shall be readily available at all times.