Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
13-205(b)(10: a turnover rate of one turnover every six (6) hours shall exist for an outdoor pool; note the flow meter reading of 100gpm
13-201(c)(3): a lavatory with tempered water shall be provided; observed no warm water in restrooms
13-189(a)(5): all pools shall be kept free from sediment, dirt, and debris; observed debris and dirt in pool
Permit/Opening
13-205(b)(1): for an outdoor pool, the turnover rate shall be one turnover ever six (6) hours; note the observed flowmeter at 120gpm
13-201(c)(3): tempered water shall exist in bathhouses; observed no hot or warm water in restrooms
13-201(c)(3) - diaper changing stations shall be made available in all bathouses; observed that restrooms did not have diaper changing stations
13-189(a)(5): pool surfaces shall be kept clean of sediment, dirt, and debris; observed that leaf debris and sediment in pool
Permit/Opening
13-189(c)(1): pH levels shall be maintained between 7.2 - 7.8; observed pH level at 6.9; CPO could never successfully achieve adequate pH range
13-188(h)(4): pool deck shall be clean and safe; observed that pool deck should be cleared of all items that might be dangerous to children
13-201(c)(3): tempered water shall exist in bathhouses; observed no hot or warm water in restrooms
13-201(c)(3) - diaper changing stations shall be made available in all bathouses; observed that restrooms did not have diaper changing stations
13-189(a)(5): pool surfaces shall be kept clean of sediment, dirt, and debris; observed that leaf debris and sediment in pool
Permit/Opening
13-205(b)(7): One turnover every six (6)hours(pools).
13-190(a)(7): Adequately sized flow meter shall be installed on return line to accurately indicate the circulation rate in gallons per minute (GPM); Observed at 140 but should be at 183.
Permit/Opening
13-202(g): An operable, hard-wired, weatherproof telephone, with direct 911 access or capability installed in a conspicuous location shall be readily available at all times with the pool enclosed(NO Cellphones!). Observed the emergency phone is not working.
13-189(c)(1): The pool shall be maintained in an alkaline condition 7.2-7.8. Observed pH at 7.0 first reading and 7.1 second reading.
13-205(b)(7): One turnover every six (6)hours(pools).
13-190(a)(7): Adequately sized flow meter shall be installed on return line to accurately indicate the circulation rate in gallons per minute (GPM); Observed at 140 but should be at 183.
Re-inspection
13-190(a): Sand filter tanks shall function properly. OBS: Sand filter in the back is leaking water.
13-188(h)(3): Rough & Abrasive surfaces prohibited. OBS: there are cracks on the side where entrance is located. Also, there is an elevated piece of concrete on the left side nearer to the deeper end that can be a hazard.
13-201(c)(3): A bathroom with tempered water with range of 70-104 degrees shall be provided. Observation: No hot water in sinks for men & women's bathroom.
13-201(b): Shower with tempered water range of 70-104 degrees shall be provided.
Observation: No hot water in deck shower.
13-189(a)(5): Pool surfaces shall be kept free of dirt by frequent brushing. Obs: Visible stains mainly in the deeper end of the pool.
Routine
13-202(g): An operable, hard-wired, weather proof phone must be installed and ready at all times. Obs: Phone inoperable. It was wet. Makes clicking sounds.
13-197(i): No disinfectant added by hand as sole or primary method of disinfection. OBS: Found chlorine tablets in 2 skimmers. They both located on the side closest to the entrance.
13-190(a): Sand filter tanks shall function properly. OBS: Sand filter in the back is leaking water.
13-190(a)(7): Adequately sized flow meter shall be installed on return line. OBS: Flow meter max value must be 1.5x of turnover rate. Turnover rate is 183.3. Max value should be 275. Max value currently is 240.
Unsecured handrails considered imminent health hazard. OBS: The handrail located on the shallow end is loose.
13-188(h)(3): Rough & Abrasive surfaces prohibited. OBS: there are cracks on the side where entrance is located. Also, there is an elevated piece of concrete on the left side nearer to the deeper end that can be a hazard.
13-201(c)(3): A bathroom with tempered water with range of 70-104 degrees shall be provided. Observation: No hot water in sinks for men & women's bathroom.
13-201(b): Shower with tempered water range of 70-104 degrees shall be provided.
Observation: No hot water in deck shower.
13-189(a)(5): Pool surfaces shall be kept free of dirt by frequent brushing. Obs: Visible dirt/stains mainly in the deeper end of the pool.
Permit/Opening
13-190(a)(7): Adequately sized meter shall be installed on the return line. Obs: flow meter range is at max 240 gpm. According to turnover rate (183.3). Their max range should be 274.5 (or 275).
13-201(c)(3): A bathroom with tempered water with range of 70-104 degrees shall be provided. Observation: No hot water in sinks for men & women's bathroom.
13-201(b): Shower with tempered water range of 70-104 degrees shall be provided.
Observation: No hot water in deck shower.
13-189(a)(5): Pool surfaces shall be kept free of dirt by frequent brushing. Obs: Visible dirt/stains throughout, mainly around inlets.
Permit/Opening
13-190(a)(4): Main drain openings must be covered by an approved, secured grating, removed only by a tool.
Observation: While CPO was switching pump on/off, to get backwash to operate, 1 one of the main drain covers came loose.
13-189(c)(1): pool must have pH of 7.2-7.8 Observation: pH was initially 7.1. After adjustment, still 7.1.
13-190(a): equipment shall operate to maintain minimum turnover.
Observation: Initial turn over rate was insufficient (needs to be 194) and was at 180. Even after backwashing, it increased but not above minimum requirement of 194.
13-190(a): equipment shall be operated to obtain minimum required turnover. Observation: Flow meter reading indicated turnover was insufficient.
13-191(a)(4): Direct discharge of polluted waters (filter backwash waters) shall be directed to a sanitary sewer. Observation: Backwash was inoperable.
13-201(c)(3): A bathroom with tempered water with range of 70-104 degrees shall be provided. Observation: No hot water in sinks for men & women's bathroom. Theres only a cold faucet.
13-201(b): Shower with tempered water range of 70-104 degrees shall be provided.
Observation: No hot water in deck shower.
13-189(a)(5): Pool surfaces shall be kept free of dirt by frequent brushing.
Observation: Bottom pool surface has staining; mainly around inlets.