Forest Park, Clayton County

Economy Hotel

241 FALCON DR FOREST PARK, GA 30297

Tourist
Latest score
81
Nov 20, 2025
City
Forest Park
County
Clayton
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Nov 20, 2025

Routine

Score: 816 violations

6 - premises free of pests and rodents; pesticide applied in accordance with laws, rules, and label

Regulation: 511-6-2-.13(1) - insect and rodent control

5 ptsCorrected: NoRepeat: No

Observed roaches/ evidence of roaches in multiple rooms inspected. Records have been verified advised to recontact pest control company

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: YesRepeat: Yes

Observed damaged/ stained window blinds in multiple locations, observed damaged air condition covers in Multiple rooms. Observed unapproved cooking equipment in rooms. Observed broken and damaged furniture in multiple rooms. Rooms observed 258,140,150,272, Items shall be in good condition and approved

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: YesRepeat: No

Observed soiled bed box spring in Rooms: 103,271,239,272,357,140,150. Advised PIC Washable mattress pads or covers shall be used on all mattresses/ box springs. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: YesRepeat: No

#140 observed door knob broken in restroom, restroom door is in disrepair, rest room ceiling is in need of repair.#150 light shield loose from wall, ceiling in restroom is in disrepair, tub in need of resurfacing. #272 sink counter in disrepair, on walls in restroom. #357 Tub in disrepair, floor is sinking at tub. # 359 Tub in need of resurfacing. #358 ceiling in restroom is in disrepair, wall in shower in need of repair. Observed walls, tubs and ceiling in restrooms in need of repair in the other following rooms 271,276,230,126,103,111,200,212,226,239,210

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: YesRepeat: No

Observed signs of mildew on ceiling and walls in the following rooms 258,263,239,271,140,150. Rooms shall be free of mildew and mold build up

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: YesRepeat: Yes

Observed ceiling with damage or stains present in rooms 203,111,115,140,150,210,359,258,. Advised shall be in good repair

Jun 16, 2025

Routine

Score: 836 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: YesRepeat: Yes

Observed damaged window blinds in multiple locations, observed damaged air condition covers in Mutiple rooms. Observed broken and damaged window at rooms 241.Observed unapproved cooking equipment in rooms:115, 215,207231,235, 237, 176. Items shall be in good condition and approved

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: YesRepeat: Yes

Observed soiled bed box spring in all rooms inspected. Rooms: 115, 225,215, 207,126, 229, 233,235,237,241,158, 160, 176. Advised PIC Washable mattress pads or covers shall be used on all mattresses/ box springs. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(1) - grounds graded, walkways, driveways

3 ptsCorrected: YesRepeat: Yes

Observed damaged wall pilers/columns in multiple areas. Observed damaged floor deck with exposed concrete re-bar on second floors of building A and B. Hotel structures shall be in good condition

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: YesRepeat: Yes

Observed tubs, light fixtures, in need of repair in rooms:115,225, 215, 207, 126, 2,29, 231, 233,235,237, Advised PIC Toilet rooms and fixtures must be smooth and

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed signs of mildew on ceiling and walls in the following rooms 215,126,229,158,160. Rooms shall be free of mildew and mold build up

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: YesRepeat: Yes

Observed ceiling with damage or present in rooms 115, 233,235,160,176. Advised shall be in good repair

Oct 21, 2024

Routine

Score: 837 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed damaged window blinds in multiple locations, observed damaged air condition covers in Mutiple rooms. Observed broken and damaged window at rooms 220 and 224. Items shall be in good condition

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed severe staining on mattresses for rooms: 154,215,216,218,105. Advised PIC Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(3) - areas in good repair/appropriate storage

3 ptsCorrected: NoRepeat: No

Observed loose handrail at stairs near dumpster end. Observed damaged wall pilers/columns in multiple areas. Hotel structures shall be in good condition

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Observed tubs, light fixtures, in need of repair in rooms: 244, 106,105, 216,218,156,154,247,265. Observed vanity unit in disrepair for rooms: 154,106,105,216,218,215,156 Observed shower facet in room: 244 does not turn off. Advised PIC Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed no ventilation in bathrooms for rooms: 244,156,214,216,218,105,154,253. Advised PIC Toilet, lavatory and bathing facilities shall be mechanically ventilated

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

Observed signs of mildew on ceiling and walls in the following rooms 244,154,265,214,216,218,105. Rooms shall be free of mildew and mold build up

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed ceiling with damage or present in rooms 215,148,156,216,218,106,105. Observed build up on wall or on base boards in rooms 371,244,154,247,253,265,215,148,156,214,216,218,106,105. Advised shall be in good repair

Feb 23, 2024

Re-inspection

Score: 806 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: Yes

Observed hot water measuring above 120 degrees F in rooms 373 (124F), 369 (123F), 272 (124F), 260 (144F), 101 (137F), 104 (126F), 106 (134F), 110 (130F), 200 (133F), 204 (129F). Advised PIC hot water is guest rooms shall not exceed 120 degrees F

3 - hot/cold running water under pressure in all required locations of tourist accommodation

5 ptsCorrected: NoRepeat: Yes

Observed only intermittent hot water in room 218. Advised PIC to repair today & occupant relocated to room with hot water

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed severe staining on mattresses for rooms: 104, 101, 110, 200, 216. Advised PIC Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Observed tubs, light fixtures, in need of repair in rooms: 373, 369, 272, 212, 216, 101, 106. Observed vanity unit in disrepair for rooms: 373, 369, 212. Observed active leak in bathtub facet in room: 214. Advised PIC Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed no ventilation in bathrooms for rooms: 373, 369, 200, 101, 104, 106, 110, 260. Advised PIC Toilet, lavatory and bathing facilities shall be mechanically ventilated

24 - openings to outside and physical facilities protected by tight-fitting doors, screening, or other means

Regulation: 511-6-2-.13(3) - insect and rodent control-openings

2 ptsCorrected: NoRepeat: No

Observed visible light entry at front-door of units, for rooms: 204, 216, 218, 101, 104, 106, 110. Advised PIC Openings to the outside shall be effectively protected against the entrance of rodents and insects by tight-fitting doors, closed windows, screening, controlled air currents or other means. Screen doors shall be self-closing and screens for windows, doors, skylights, transoms and other openings to the outside shall be tight-fitting and free of breaks

Jan 24, 2024

Routine

Score: 6811 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: Yes

Observed hot water measuring above 120 degrees F in rooms 373,260, 162, 206, & 220. Advised PIC hot water is guest rooms shall not exceed 120 degrees F

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

Observed no hot water at hand sink in room 218. Advised PIC to repair today & occupant relocated to room with hot water

6 - premises free of pests and rodents; pesticide applied in accordance with laws, rules, and label

Regulation: 511-6-2-.13(1) - insect and rodent control

5 ptsCorrected: NoRepeat: Yes

Observed roach crawling on bed in room 369. Residents reported roach activity in building A but EHS did not observe said activity at time of inspection. Advised PIC to work in conjunction with certified pest control company to abate pest activity

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed mattresses in need of repair in rooms 104 & 200. Advised PIC to repair

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(3) - areas in good repair/appropriate storage

3 ptsCorrected: NoRepeat: No

Observed railings with heavy rust throughout property. Observed ceiling in breezeway in buildings C & A in need of repair. Observed holes & cracks in pillars in building A. Advised PIC to repair

10 - permit and inspection report current and properly displayed; pic assigned

Regulation: 511-6-2-.05(7) - inspection posting

2 ptsCorrected: NoRepeat: No

Observed most recent inspection report not on display at facility. Facility had old inspection report posted. Advised PIC to post most recent inspection

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Observed tubs in need of repair or replacement in rooms 373, 106, 220, 162, 130, 110, 200, & 212. Observed missing light fixture in restrooms in rooms 373 & 362. Advised PIC to replace. Observed toilets in need of repair in rooms 206, 214, 130, & 162. Advised PIC to repair or replace. Also observed vanities in need of repair in rooms 212 & 373. Advised PIC to repair

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed ventilation in bathrooms in rooms 101, 104, 106, 110, 212, 216, 214, 373, 260, 272, & 162 in need of repair. Advised PIC must repair

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: Yes

Observed walls & ceilings in need of repair in rooms 101, 106, 110, 212, 216, 214, 373, 260, 272, & 162. Advised PIC to repair

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(3) - room ventilation

2 ptsCorrected: NoRepeat: No

Observed HVAC unit in need of repair in rooms 106, 204, & 206. Advised PIC to repair

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(2) - cooking in rooms

2 ptsCorrected: NoRepeat: No

Observed cooking equipment in rooms 101, 272, 162, 206, & 128. Advised PIC must remove immediately

Jun 20, 2023

Complaint

Score: 759 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: No

Observed hot water in guestrooms exceeding 120F. In rooms: 108(136F), 131 (121F), 138 (123F), 142 (122F), 122 (133F). Advised PIC hot water in guestrooms shall not exceed 120F

6 - premises free of pests and rodents; pesticide applied in accordance with laws, rules, and label

Regulation: 511-6-2-.13(1) - insect and rodent control

5 ptsCorrected: NoRepeat: No

Observed fly activity in room: 172 and 131. Advised PIC effective and appropriate measures shall be taken to eliminate the presence of roaches and flies, and other insects

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed a/c unit in disrepair in room 138, 131. Observed debris on a/c unit in room 108; Observed dresser in disrepair in room 138. Advised PIC that furniture shall be kept in good condition and good repair

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

Observed debris on vent (Room 138), bathroom vent in disrepair (Room 172), Bathroom ceiling in disrepair (Room 108), cracks on ceiling (Room 131 and 142), Missing light shield in bathroom (Room 108 and 172). Advised PIC all bathing facilities and fixtures shall be kept clean and in good repair

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

Observed mold along ceiling in bathroom, bathroom ventilation in disrepair, mildew present in shower in room 224. And no ventilation observed in bathroom 131 and 172. Advised PIC toilet, lavatory and bathing facilities shall be mechanically ventilated

22 - approved leak proof containers covered, in proper location, clean, and maintained; collection adequate

Regulation: 511-6-2-.12(2) - garbage and refuse containers

2 ptsCorrected: NoRepeat: No

Observed garbage dumpster lid in need of repair and missing lid. Advised PIC that the dumpster/garbage shall have a tight-sitting lid, kept in good condition and kept covered

24 - openings to outside and physical facilities protected by tight-fitting doors, screening, or other means

Regulation: 511-6-2-.13(3) - insect and rodent control-openings

2 ptsCorrected: NoRepeat: No

Observed visible light entry at entry doors in rooms 224 and 108. Advised PIC that openings to the outside shall be effectively protected against the entrance of rodents, pest, and insects by tight-fitting doors and/or screenings

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed mold along ceiling and wall in bedroom in room 224; Observed mold inside window panel in room 224; Observed wall in disrepair in room 224 (near handwash sink), observed door in disrepair in room 108; observed ceiling in disrepair in room 108; Observed debris on ceiling in room 172; Observed build up present on floor in room 172; Observed crack on ceiling above handsink in room 142; observed wall in disrepair in room 138; Observed door in disrepair in room 138; Observed minor cracks in ceiling in room 131; Observed crack in door in room 131; Observed water damage on ceiling in room 131. Advised that floors, walls, ceilings repaired

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

Observed no anti-slip mat applique or slip-strips in bathtub. In room(s) 142 and 138. Advised PIC anti-slip tub slip-strips, applique, or slip-proof mats shall be provided in each bathing facility