Dec 29, 2025
Routine
3 - hot/cold running water under pressure in all required locations of tourist accommodation
Regulation: 511-6-2-.07(2) - hot water supply
Observed water temperatures exceeding 120F in rooms 204 (124F), 212 (122F), 213 (122F), and 320 (123). C/A: Adjust and/or have temperatures adjusted to meet water requirements and not exceed 120F