MIDWAY, Liberty County

Woodland Lakes Pool

79 CLUBHOUSE DR MIDWAY, GA 31320

Pool
Latest score
91
Jun 4, 2026
City
MIDWAY
County
Liberty
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 4, 2026

Permit/Opening

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Observed no flow rate on flow meter

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing from skimmers

May 27, 2025

Permit/Opening

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed no flow rate on flow meter

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing from skimmers

Aug 1, 2024

Re-inspection

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: Yes

Observed no flow rate on flow meter

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: Yes

Observed weirs missing from skimmers

Jul 31, 2024

Routine

Score: 764 violations

5 - emergency phone operational and accessible

Regulation: 511-3-5-.23(5)(h) - (h) absence of required lifesaving equipment on the deck or an emergency phone;

15 ptsCorrected: NoRepeat: No

Observed phone not working .

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

Observed pH below 7.2. Facility's test kit was reading 8.6. The test kit had Taylor R-0004 pH indicator instead of the LaMotte 7037-G pH indicator meant to be used with kit. This is likely why the pH is not correct.

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed no flow rate on flow meter

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing from several skimmers.

Jun 12, 2024

Complaint

Score: 675 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

Observed free chlorine level of .06ppm. Minimum is 1ppm.

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Observed no flow rate registering on flow meter. Flow rate should be registering at approximately 300gpm for the required 6 hr turnover time.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

Facility does not appear to be consistently checking chlorine and pH levels and filling out logs properly.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing from 3 skimmers.

35 - operator facility inspections performed; written documentation

Regulation: 511-3-5-.22(6) - (6) written documentation of the operator’s visits must be available at the pool facility. at a minimum, the written record must indicate the condition of the following items:

4 ptsCorrected: NoRepeat: No

CPO inspection records not available on site at time of inspection.

May 30, 2024

Permit/Opening

Score: 893 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed no flow registering on flow meter.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing from all but one skimmer.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: No

Observed no sign pool hours sign posted.

Jun 30, 2023

Permit/Opening

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed flow meter did not appear to be registering any flow

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing or installed upside down on some skimmers