Mar 27, 2026
Permit/Opening
101 LEGACY WAY BRUNSWICK, GA 31525
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: .17((1)(c) - proper disinfectant level
Observed a low free chlorine level at the time of this inspection. CA: Ensure chlorine is 2.0-10.0ppm.
Permit/Opening
Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.
Observed combined chlorine above 0.4ppm at the time of this inspection. CA: Ensure combined chlorine does not exceed 0.4ppm.
Re-inspection
Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.
Observed combined chlorine above 0.4ppm at the time of this inspection. CA: Ensure combined chlorine does not exceed 0.4ppm.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed CYA level high at the time of this inspection. CA: Ensure CYA does not exceed 90ppm.
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed emergency phone inoperable at the time of this inspection. CA: Facility shall ensure emergency phone is functional at all times.
Regulation: .17((1)(c) - proper disinfectant level
Observed a high free chlorine level at the time of this inspection. CA: Ensure chlorine is 2.0-10.0ppm.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed CYA level high at the time of this inspection. CA: Ensure CYA does not exceed 90ppm.
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not working at the time of this inspection. CA: CPO stated he will replace the flow meter, ensure this is available and functioning at all times.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
CYA level high at the time of this inspection. CA: Lower CYA to 90ppm or less.
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed emergency phone inoperable at the time of this inspection. CA: Facility shall ensure emergency phone is functional at all times.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
CYA level high at the time of this inspection. CA: Lower CYA to 90ppm or less.
Permit/Opening