7870 SWEETWATER DR DOUGLASVILLE, GA 30135-5913
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
OBSERVED THE PH OVER 7.8 CA:Chemical Values: pH 7.2 7.4-7.6 7.8 Alkalinity (buffering), 60 ppm 80-100 halogens compounds with high pH 180 ppm as CaC03 100-120 halogen compounds with low pH Calcium hardness, ppm, CaCo3 150 200-400 to balance water 1000
Regulation: 511-3-5-.10(1)(a) - (a) pools shall use wall or floor inlets that are adequate in design, number and location to provide adequate mixing.
OBSERVED MISSING RETURN INLETS COVERS CA: Pools shall use wall or floor inlets that are adequate in design, number and location to provide adequate mixing.
Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.
OBSERVED MISSING TRAINING CERTIFICATION . CA:The trained operator shall have a current certificate showing completion of an approved operator training course. A copy or the original certificate or documentation shall be available onsite for inspection by the Health Authority.
Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
OBSERVED NO INSPECTION REPORT PLACED IN PUBLIC VIEW CA: The operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
Routine
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
FLOW METER DOES NOT APPEAR TO BE WORKING. CA: REPAIR OR REPLACE.
Permit/Opening
Routine
Regulation: 511-3-5-.23(5)(f) - (f) broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate
EQUALIZER COVERS NON-VGB COMPLIANT. ENTIRE POOL MUST ALWAYS BE VGB COMPLIANT.