May 18, 2026
Permit/Opening
19 - adequate turnover rate
13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain minimum required turnover rate. Observed pool at 250 GPM, pool should be reaching 361 GPM.
1307 GRIFFITH PARK RD DECATUR, GA 30030
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain minimum required turnover rate. Observed pool at 250 GPM, pool should be reaching 361 GPM.
Permit/Opening
13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain minimum required turnover rate. Observed pool at 200 GPM, pool should be reaching 361 GPM.
Re-inspection
13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain minimum required turnover rate. Observed pool at 200 GPM, pool should be reaching 361 GPM.
13-187(c): The current inspection report shall be posted in a conspicuous place so that it is easily readable. Current inspection was not posted.
13-187(c): The operating permit shall be framed and displayed in a conspicuous place. Operating permit was not observed.
Routine
13-202(g): An operable, hardwired, weatherproof phone with direct 911 access or capability shall be readily available. Pool phone was observed to ring and cut off on a consistent basis and unable to access 911 operator.
13-189(c)(1): The free chlorine residual in all parts of the pool shall be maintained at a concentration of no less than 3ppm and shall not exceed 10ppm. The pool was observed with no chlorine in the pool, 0.06ppm.
13-187(c): The operating permit shall be framed and displayed in a conspicuous place. Operating permit was not observed.
Routine
13-190(a): the equipment shall be operated continuously on a twenty-four (24) hour basis. Observed that adequate turnover rate was not met.
Routine
13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate circulation rate in gallons per minute.