May 29, 2026
Permit/Opening
1 LAKEVIEW WAY JONESBORO, GA 30238
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Re-inspection
Routine
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
Observed two entry gates not self-closing/self-latching. Advised to repair.
Regulation: .17(1)(a)(b) - proper disinfectant level
Observed chlorine level above 100ppm. Advised PIC chlorine shall read between 2-10ppm.
Permit/Opening
Regulation: 511-3-5-.08(6) - (6) all piping shall be marked with directional arrows as necessary to determine flow direction. all piping in the equipment room shall be permanently identified by its use and the pool and or aquatic feature it serves.
Observed piping in the pump room not marked. COS: Pipes marked.
Routine
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Observed "No Diving" in 2 inch lettering. Advised to install in 4 inch lettering. Also, missing universal No Diving symbol. Advised to install
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed grabrail loose near steps. Advised to tighten.
Permit/Opening
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Observed "No Diving" in 2 inch lettering. Advised to install in 4 inch lettering. Also, missing universal No Diving symbol. Advised to install
Permit/Opening