May 29, 2026
Re-inspection
700 PAIGE LN WOODSTOCK, GA 30189
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Permit/Opening
Regulation: 511-3-5-.23(5)(d) - (d) the water turbidity is such that the suction outlet/main drain cover or a standard white marker tile on the bottom of the deepest portion of the pool cannot be seen.
Observed pool very cloudy. Unable to see the bottom of the pool or main drains. 511-3-5-.23(5)(d) - (d) The water turbidity is such that the suction outlet/main drain cover or a standard white marker tile on the bottom of the deepest portion of the pool cannot be seen. (d) The water turbidity is such that the suction outlet/main drain cover or a standard white marker tile on the bottom of the deepest portion of the pool cannot be seen.
Routine
Permit/Opening
Routine
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed turn over rate low. Flow meter read 70gpm. Turn over rate should be min 81 gpm
Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Chemical must be checked twice a day by volunteer and CPO must check twice a week and make necessary adjustments.
Re-inspection
Permit/Opening
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Address not registered with 911.
Routine
Permit/Opening