CANTON, Cherokee County

Providence Walk

434 PROVIDENCE WALK ST CANTON, GA 30114

Pool
Latest score
100
May 15, 2026
City
CANTON
County
Cherokee
Inspections
8

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 15, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jul 30, 2025

Routine

Score: 942 violations

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

Observed no daily logs for water testing. Must be completed and documented daily by trained operator or responsible person per DPH Rule

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

Inspection report not posted in public view.

Jul 30, 2025

Routine

Score: 705 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

There was no chlorine present at the time of routine inspection. Free Chlorine level in pools using cyanuric acid or a stabilized chlorine product; Minimum 2.0 Ideal 2.0-5.0 Maximum 10.0. Immediate pool closure.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Flow meter was not in operation at the time of inspection. A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided.

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

Observed no daily logs for water testing. Must be completed and documented daily by trained operator or responsible person per DPH Rule

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Certification not posted inside the facility.

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

Inspection report not posted in public view.

May 8, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jun 20, 2024

Routine

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed a turnover rate of 0 gpm. The required turnover rate for this pool is 149 gpm.

Mar 27, 2024

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jul 30, 2023

Routine

Score: 942 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Flow meter is reding below 100 gpm. The turnover rate for this pool is 149 gpm.

34 - inspection report placed in public view

Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

1 ptsCorrected: NoRepeat: No

Inspection report not posted in public view.

May 17, 2023

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.