Savannah, Chatham County

Red Roof Inn

11750 ABERCORN ST SAVANNAH, GA 31419

Tourist
Latest score
76
May 13, 2026
City
Savannah
County
Chatham
Inspections
5

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 13, 2026

Routine

Score: 767 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: No

Observed hot water in room 254 at 122 degrees F.

RCA: The water temperature at the water heater shall be adjusted to accommodate proper hot water temperatures. Rule: In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120 degrees F

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Observed no gas fire equipment form on the premise and PIC unable to provided proof of inspection.

RCA: Gas fired inspection form left form with the PIC. Discussion with owner advised if proof inspection was not provided by end of day, inspector will follow later this week to have inspection scheduled on site. Email and direct line provided for the report to be submitted to the Health Authority upon completion. Rule: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed build-up of food debris in the mini fridge of room 254. Observed build-up of food debris, a water bottle and plastic bag in the mini fridge of room 256. Observed tears in the curtains of both rooms inspected. Observed dirt and debris in the under the sink cabinet in room 256.

Rule: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observations for room 254: Staining to the pillows and pillowcases, the comforter, sheets, and duvet/cover sheet. Observations for room 256: Staining to the comforter, and hairs on the flat and fitted sheets.

RCA: Advised PIC to have beds stripped and remade with clean linens. Rule: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

24 - openings to outside and physical facilities protected by tight-fitting doors, screening, or other means

Regulation: 511-6-2-.13(3) - insect and rodent control-openings

2 ptsCorrected: NoRepeat: No

Observed gaps at the entry doors to both rooms inspected (254 and 256).

Rule: Openings to the outside shall be effectively protected against the entrance of rodents and insects by tight-fitting doors, closed windows, screening, controlled air currents or other means

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed the ceiling to be cracked and damaged in room 254. Observed dirt, debris and articles of clothing (socks) on the floors behind furniture in the both rooms.

Rule: Floors, walls, ceilings. windows, doors and all other appurtenances shall be of sound construction, properly maintained in good repair and shall be kept clean

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(3) - room ventilation

2 ptsCorrected: NoRepeat: No

Observed build-up of dust and debris on the vents of the A/C units in both rooms.

Rule

Sep 26, 2025

Routine

Score: 836 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Observed no gas fire equipment form on the premise.

RCA: Informed PIC to have inspection done and form complete annually. Left form for PIC. All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Observed dirty lamp shade with black substance in room 138 Observed dirt build up under desk in room 138 Observed debris in mini-fridge in room 138 Observed debris build-up in chair in room 138

RCA: Informed PIC to replace lamp shade, clean dirt under desk, in the chair, and mini-fridge. All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed staining on mattress cover in rooms 252, 242 Observed cigarette burns on linens in room 252 Observed top layer of mattress ripped off exposing springs, foam and mattress internals in room 138.

RCA: Informed PIC of staining and mattress and recommended to replace mattress that is separating. Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed food stains on walls, debris under table and floors in rooms 252, 138.

RCA: Informed PIC to ensure housekeepers are sweeping in appropriate areas and wiping walls with food stains. Floors, walls, ceilings. windows, doors and all other appurtenances shall be of sound construction, properly maintained in good repair and shall be kept clean

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

Observed anti-slip bathroom mats in rooms 252, 242 to be peeling up from the tub surface.

RCA: Informed PIC to replace the anti-slip covers in appropriate rooms. Anti-slip tubs slip strips, appliqués, or slip-proof mats shall be provided in each bathing facility and shall be kept clean and in good repair

33 - housekeeping carts and storage areas maintained; clean/sanitized items protected from contamination

Regulation: 511-6-2-.17(2) - housekeeping carts

1 ptsCorrected: NoRepeat: No

Observed housekeeping carts to not have common name labels on cart chemicals.

RCA: Informed PIC to ensure common name labels are on spray bottles. Any spray bottle used in cleaning a tourist room or stored on the housekeeping cart shall be labeled with its contents. Cleaners and sanitizer shall be used according to the manufacturer’s use direction and label

May 6, 2025

Routine

Score: 805 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: No

Observed hot water temperatures exceeding 120 degrees F in rooms 133 (126F) and 233 (126F).

RCA: Hot water in all guest rooms shall not exceed 120F

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Observed facility to not have a completed gas-fired equipment form on file. Discussion with staff was that the inspection was required as part of re-opening with, they do not know where the paperwork is.

RCA: A blank gas-fired equipment inspection report was provided to the PIC at the time of inspection. Staff notified that inspection shall be done annually and documentation shall remain on file at the facility. All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Observed old food debris in the microwaves in rooms 133, 233, and 249. Observed food debris in the mini fridge of room 133. Observed food left by previous tenant in rom 233.

RCA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed staining to comforter in rooms 133, 233, 252. Observed staining to the pillowcases in rooms 133, 249. Observed staining to the mattress pad in room. 249 Observed a hole in the pillowcase in room 233. Observed dust/debris on the mattress pad in room 252. Observed tears to the comforter in room 252.

RCA: PIC shall replace all staining bedding. Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(3) - room ventilation

2 ptsCorrected: NoRepeat: No

Observed dust & debris build-up on the A/C unit vents in all rooms inspected.

RCA: PIC shall ensure A/C unit vents are cleaned regularly

Feb 29, 2024

Routine

Score: 826 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Observed facility to not have a completed gas-fired equipment form on file. RCA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed microwave to be heavily damaged in room 129. Observed old food debris in microwave in rooms 239 and 230. Observed burns/ holes in curtains in room 239. RCA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed staining and holes on bedding in all rooms inspected. Observed staining on mattress protectors ( 239, 221, 230 and 129), Hair and black debris on mattress in room 221. RCA: PIC shall replace all staining bedding. Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Observed light fixture cover to be broken and piece missing in room 129. Observed holes in the wall near bathroom entrance in room 229 and holes and rust colored staining on walls in main room of 117. RCA: RCA: Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

Observed black mold-like growth on bathroom ceiling in room 117. RCA: oilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

33 - housekeeping carts and storage areas maintained; clean/sanitized items protected from contamination

Regulation: 511-6-2-.17(2) - housekeeping carts

1 ptsCorrected: NoRepeat: No

Observed none of the housekeeping carts to be labelled with the contents within the bottle. RCA: Any spray bottle used in cleaning a tourist room or stored on the housekeeping cart shall be labeled with its contents

Sep 8, 2023

Routine

Score: 806 violations

1 - adequate, approved, permitted, protected potable water supply; no cross connection or back siphonage

Regulation: 511-6-2-.07(2) - water supply and sanitizing

5 ptsCorrected: NoRepeat: Yes

Observed hot water to exceed 120F in rooms 144, 215, 246, 126 and 130. RCA: In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Observed facility to not have a completed gas-fired equipment form on file. RCA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Observed staining on bedding in all rooms inspected. Observed staining on mattress protectors ( 144, 230, 201), Hair on and heavy staining on mattress in 215 and staining on pillows in all rooms inspected. RCA: PIC shall replace all staining bedding. Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

10 - permit and inspection report current and properly displayed; pic assigned

Regulation: 511-6-2-.05(7) - inspection posting

2 ptsCorrected: NoRepeat: Yes

Observed facility to not have inspection report posted. Inspection report was posted on the side table in the through hallway. RCA: PIC shall post the inspection report in public view. Any tourist accommodation inspection report addendum(s), completed by the Health Authority to document observations, violations, and corrective actions resulting from an inspection need not be displayed, but must be made available by the tourist accommodation operator to the public upon request

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

Observed bathrooms in rooms 201 and 215 to have holes and indentation in the walls. PIC was shown the damage and when he pressed on the wall it broke (dry rotting). The rooms were taking out of the rotation to be gutted and fixed. RCA: Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(3) - room ventilation

2 ptsCorrected: NoRepeat: Yes

Observed heavy build up on air conditioning filters in rooms 201, 246 and 230. RCA: PIC shall clean or replace filters. Rule: Ventilation shall be provided for all rooms. Where ventilation is provided by means of windows, they shall open directly to the outside air and the openable window area of each room shall be not less than 1/20 of the floor area served. Where ventilation is provided by other means, it shall comply with the requirements of the current International Mechanical Code with Georgia Amendments or future subsequent revisions adopted thereafter to provide comfortable living conditions, remove objectionable odor and fumes, and prevent excessive condensation. Ventilation systems shall comply with applicable State and local fire prevention requirements and building codes