May 6, 2026
Permit/Opening
123 CLUB HOUSE CIR SAINT MARYS, GA 31558
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
At time of inspection, the cyanuric acid (CYA) level registered at 196 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water, until CYA is below 90 ppm.
Permit/Opening
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
At time of inspection, the cyanuric acid level registered at 104 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water.
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
At time of inspection, the emergency phone was not operational. CPO contacted management and the phone was fixed during the course of the inspection.
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
At time of inspection, the flow rate is lower than required. CPO states he will clean the filters thoroughly and troubleshoot why the flow rate is so low, causing the turnover to be low.
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
At time of inspection, observed the flow meter not functioning. CPO states bid has been submitted to replace all flow meters and gauges, as they are all old.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
At time of inspection, the cyanuric acid level registered at 101 ppm (CYA must be 90 ppm or less). CPO will drain some water and add fresh water to lower CYA.
Permit/Opening