Jul 22, 2025
Routine
6 - proper disinfectant level
CHLORINE TOO LOW
7 - ph between 7.2 and 7.8
pH TOO HIGH
19 - adequate turnover rate
FLOW RATE TOO LOW
34 - inspection report placed in public view
INSPECTION REPORT NOT DISPLAYED
1000 REDWOOD LN ATHENS, GA 30606
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
CHLORINE TOO LOW
pH TOO HIGH
FLOW RATE TOO LOW
INSPECTION REPORT NOT DISPLAYED
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
FLOW METER IS OUT.
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Free chlorine ranging from 16-20 ppm. Ensure levels are between 2-10ppm.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter is out
Permit/Opening
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
TURNOVER RATE IS LOWER THAN REQUIRED 59 GPM
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
FREE CHLORINE BELOW 2.0PPM MINIMUM.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
FLOW METER IS OUT
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
MISSING PEAK OCCUPANCY SIGNAGE (12 PEOPLE)