Valdosta, Lowndes County

New Valdosta Inn

2015 W HILL AVE VALDOSTA, GA 31601

Tourist
Latest score
85
Jun 15, 2026
City
Valdosta
County
Lowndes
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 15, 2026

Routine

Score: 854 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Facility unable to to provide copy of gas fired equipment form. Please have testing done and send documentation to Kristen.Tyler@dph.ga.gov

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 210- Observed stains on lamp shade in room.; Room 105- Observed stains on lamp shade in room.; Room 108- Observed headboard upholstery with large arounds of scratches. Observed tears on upholstered chair in room. Stains observed on sofa bed in room. Handles missing off dresser in room. Counter top of sink broken with large crack

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 108- Observed stains on sheets and mattress.; Room 105- Observed stains on on sheets on both beds.; Stains on pillow.; Room 210- Observed box spring cover heavily soiled with stains. Observed stains on sheets. Observed cigarette burns in the comforters and sheets

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: Yes

Room 108- Observed evidence of water damage on room in ceiling.; Room 203- Observed gap in tile around shower knob in bathroom. Room 210: Observed baseboards in need of cleaning in room 105, 108, 203.; Room 105- Observed a lot of trash under sinks in cabinet under sink. Trash observed inside tv dresser drawers. Room 210- Observed trash under bed

Dec 15, 2025

Routine

Score: 855 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 102 &110-Decor pictures observed with moldy/mildew stains. Observed staining in upholstered sofa. Room 102- observed damage to upholstered head board, stains on lamp shades, and stains and crumbs inside sofa bed. Room 209- Observed torn upholstered chair. Room 110- Observed damage lamp shade. Observed missing knobs on night stand

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 110- Observed cigarette burns in mattress pad on bed. Room 209- Observed cigarette burns in comforter of bed and discoloration on sheets. Also observed stains on pillows, mattress pads, and sheets

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(1) - grounds graded, walkways, driveways

3 ptsCorrected: NoRepeat: No

Observed hole in pillar closest to Burger King at the end of the building. -Observed missing soffit vinyl siding on second floor of motel. -Observed damage to top side of building closest to laundry room

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Room 102- Observed evidence of water damage on room in ceiling. Damage/mold in ceiling in shower. Room 110- Observed evidence of water damage on ceiling. Observed hole in ceiling in shower. Room 204- Observed damage to baseboards behind door in room

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(4) - room lighting

2 ptsCorrected: NoRepeat: No

Room 209- lighting and electrical not working in restroom & sink area. Ventilation vent in the rest room was observed hanging. Room 110- Observed light fixture without covering. Room 204- Observed missing smoke detector

Jun 25, 2025

Routine

Score: 903 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 104- Staining was observed on lamp shades, upholstered green head board in disrepair with tears, small stains observed on curtains. Room 116- Upholstered chairs observed with stains, and staining on lamp shades. Room 124- Staining was observed on upholstered seat, upholstered green bed headboard in disrepair with tears

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 104- observed stains on sheets and burns on comforter. Room 116- Observed comforter with cigarette burn holes and paint stains on the sheets. Room 124- Observed cigarette burn marks on the pillows, sheets and mattress pad

26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved

Regulation: 511-6-2-.14(3) - room ventilation

2 ptsCorrected: NoRepeat: No

Room 124- Observed missing smoke detector with plastic cup stored in place of smoke detector. Room 116- has mini fridge that is rusted on the top of it

Dec 16, 2024

Routine

Score: 865 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 108- Head board in need of reupholstering, chair at desk has tears in upholstery. Lamp shade in need of replacing. Room 110- observed wax stains on upholstered chair in room. Light shade in need of replacing

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 108- Observed stains on fabric on upholstered sofa. Observed stains on mattress protectors and sheets

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(3) - areas in good repair/appropriate storage

3 ptsCorrected: NoRepeat: No

Observed damage (holes in stucco) to outside pillars if building on first floor closest to burger king

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: Yes

Room 108- Door leaded to bathroom is swelling at bottom; Observed mold on ceiling near sofa chair

33 - housekeeping carts and storage areas maintained; clean/sanitized items protected from contamination

Regulation: 511-6-2-.17(2) - housekeeping carts

1 ptsCorrected: NoRepeat: No

Observed stains on clean and folded sheets stored in the housekeeping/laundry storage area

May 20, 2024

Routine

Score: 816 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility unable to produce most current gas fired inspection report. PIC was able to product report for recharging of fire extinguishers etc. PIC stated fire extinguishers and gas fired equipment was conducted on same day. *Send documentation to Kristen.Tyler@dph.ga.gov of gas fired equipment inspection. If not conducted have gas fired equipment inspection conducted

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 203- Was closed for maintenance. Has apparent water damage from leak in ceiling. Room 212- carpet has mildewy smell and in need of replacement. Dresser in need of knob replacement and broken leg on dresser under television

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 212- has small amount of staining on comforters and sheets; Room 222R- has large staining on mattress pad and mattress. Multiple nails drilled outwards at bottom of bad frame which could pose safety hazard

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

2 ptsCorrected: NoRepeat: Yes

Room 212- Dresser drawer has a lot of trash inside, needs cleaning. Clean corners of all observed rooms and in tubs

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Room 214- Ventilation vent in bathroom is not operating; Cover is missing off of ventilation vent in rest room. Room 222R- mold was observed on popcorn ceiling in room in front of sink and in bathroom above shower; Room 218- was closed for maintenance. A large amount of mold was present on wall behind entry door and on ceiling. Room 203- Was closed due to roof leak and caving of ceiling. Mold was present on insulation near room leak and in freezer/fridge combo; Room 212-ventilation system is bathroom is not working

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Room 214- Holes were observed in walls throughout room and paint was peeling off ceiling in corner of room near door; Room 203- was closed due to maintenance hole in ceiling due to roof leak; Room 222R- Hole in wall observed near outlet near front window; Cable outlet face plate removed and outlet was filled with cloth. Wall was dimpling near bathroom. Smoke and sut observed on top of bathroom door frame

Dec 18, 2023

Routine

Score: 835 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility is not able to produce documentation for most current gas fired inspection report. PIC stated owner has it at personal office. Discussed with owner. *Send documentation to Kristen.Tyler@dph.ga.gov of gas fired equipment inspection. Must be kept on site at facility for viewing by Health Authority

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 125R- Towel rack missing

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

Room 104- Comforter on bed has holes, sleeper sofa has small stains on cushions; Room 106- Curtains have staining, Clean sleeper sofa, Sheets on bed have stains, Mattress pad has cigarette burns; Room 105- Staining on mattress, Staining on box spring, Staining on mattress pad, Replace pillow cases, has spider webs.; Room 125R staining on curtains, sheets have stains, clean recliner chair,

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Room 104- Shower needs to be cleaned in corners, build up of debris, room also has dirt debris in corners; Room 125R- Needs cleaning of dirt, dust, in corners of room, underneath AC unit, recliner chair needs cleaning; Room 105- Clean air vents on AC Unit; Room 106- Clean freezer portion of mini fridge excessive ice build up. Clean sleeper sofa from dirt and debris

17 - proper ventilation; no sign of mold, mildew, odors or moisture

2 ptsCorrected: NoRepeat: Yes

Room 106- Ventilation vent is bathroom is non operation; Room 106- extra mini fridge in room has mold/mildew inside; Room 125R- Vent cover is missing and on tire rack;

Jun 27, 2023

Routine

Score: 739 violations

6 - premises free of pests and rodents; pesticide applied in accordance with laws, rules, and label

Regulation: 511-6-2-.13(1) - insect and rodent control

5 ptsCorrected: NoRepeat: Yes

Room 102- Observed spiders in room and well as bugs on bed; Room 112H observed spiders in room; Room 108- Observed dead roach on floor; Room 118-Observed spider webs and insects

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility is not able to produce documentation for most current gas fired inspection report

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Room 112H- Sleeper sofa had excessive amounts of dog hair; Room 108- Old gummy/candy present inside sleeper sofa; Room 102- had old hair in sleeper sofa

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Room 118- Mattress was heavily soiled with large stains, comforter in room had cigarette burns and stains on sheets; Room 114- Mattress had mold and stains

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

3 ptsCorrected: NoRepeat: Yes

Observed walk ways through out grounds soiled with litter and debris

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

Room 108- Fecal Matter observed in toliet, restroom needs cleaning; Room 112H bottom of toliet near floor needs cleaning

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(6) - artificial light

2 ptsCorrected: NoRepeat: Yes

Room 112H- Light cover was off of light in restroom

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Room 102- Ventilation Vent is non operational; Room 102- Mold is present on ceiling above shower; Room 114- Shower curtain has mildewy smell. Room 114- Mold is present on back of bathroom door; Room 118- Shower head is moldy/mildewy

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: Yes

Room 102- Hole is present in bathroom door, walls need repainting and cleaning. Room 118- Walls need cleaning and painting, missing floor board where floor in front of sink meets bathroom floor; Room 108- Ceiling in disrepair and has hole above shower, Bathroom door is swelling/splitting at bottom. Floor boards missing where flooring in front of sink and bathroom floors meet.;