Apr 2, 2026
Permit/Opening
106 KING ST BREMEN, GA 30110
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Routine
Permit/Opening
Re-inspection
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter reading 130gpm. CA: PIC will have flow rate increased to at least 145gpm.
Re-inspection
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed pH level at 6.7. CA: Pool will not be opened until the pH reaches at least 7.2.
Routine
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed low turnover rate(130gpm). CA: PIC will backwash pool and increase turnover rate to at least 130gpm.
Routine
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed cyanuric acid levels of 130ppm. CA: PIC will maintain cyanuric acid levels at or below 90ppm.
Permit/Opening
Routine
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed low turnover rate for pool(130gpm).
Routine
Re-inspection
Routine
Regulation: 511-3-5-.23(5)(c ) - (c) the pump, automatic disinfectant equipment, or other equipment necessary for continuous filtration and disinfection of the swimming pool, spa, or recreational water park attraction is not working or is unable to maintain adequate turnover rate.
Observed no working dispensing system for pool chemicals.
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed low turnover rate for pool (130).