Albany, Dougherty County

Towneplace Suites by Marriott

3014 KENSINGTON CT ALBANY, GA 31707

Tourist
Latest score
92
May 27, 2026
City
Albany
County
Dougherty
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 27, 2026

Routine

Score: 924 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed the carpet in room 104 not in good repair. CA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin. PIC will have the carpet repaired

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

4 ptsCorrected: NoRepeat: No

Observed the interior of the refrigerators in rooms 406, 410, and 412 not clean. CA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin. PIC will have the refrigerators cleaned

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed the mattresses stained in rooms 107, 410, and 412. CA: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly. PIC will have the mattresses cleaned

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed the mattresses stained in rooms 107, 410, and 412. CA: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly. PIC will have the mattresses cleaned

Jan 23, 2026

Routine

Score: 913 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Observed no current gas fired equipment inspection for the hotel. CA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency. PIC will have the inspection done

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed the interior of the RIF not clean in room 300. CA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin. PIC will have the room cleaned

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed the carpet in rooms 301 and 404 not in good repair. CA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin. PIC will have the carpet repaired

Jun 25, 2025

Routine

Score: 942 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed the curtains in rooms (200 and 208) not in good repair. CA: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin. n PIC will have the curtains replaced

22 - approved leak proof containers covered, in proper location, clean, and maintained; collection adequate

Regulation: 511-6-2-.12(2) - garbage and refuse containers

2 ptsCorrected: NoRepeat: No

Observed no drain plug for the dumpster. CA: All outside refuse or garbage storage containers shall be constructed of durable metal or other approved types of materials, which do not leak and do not absorb liquids and shall be provided with tight-fitting lids or covers and shall be kept covered when stored. PIC will have the drain plug replaced

Dec 3, 2024

Routine

Score: 951 violation

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Observed no gas fired equipment form on fie. CA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency. PIC will have the inspection completed

Jul 17, 2024

Routine

Score: 874 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Observed gas fired equipment inspection on file. CA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency. PIC will have gas fired equipment inspected

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed mattress stained in room 303. CA: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. PIC will replace mattress

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

Observed faucet loose in the bathroom of room 307. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. PIC will have faucet secured in place

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

Observed the appearance of mildew or mold stains on the ceiling of room 306 and the laundry room. CA: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. PIC will have mold removed

Jan 22, 2024

Routine

Score: 991 violation

14 - single service items placed in guestrooms or dwelling units commercially pre-wrapped

Regulation: 511-6-2-.07(6) - single service items

1 ptsCorrected: NoRepeat: No

Observed unwrapped single service lids in rooms 404,409, and 410. PIC will have lids replaced with commercially pre-wrapped lids to protect against contamination

Sep 11, 2023

Routine

Score: 887 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

Observed holes in curtains in room 207, 320, and 422. PIC will have curtains replaced

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed stain sheets on bed in room 322

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed ripped sheet on right bed in room 422. PIC will replaced ripped fitted sheet

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed hair on bedding in rooms 109 and 322. PIC will replace bedding in the room

24 - openings to outside and physical facilities protected by tight-fitting doors, screening, or other means

Regulation: 511-6-2-.13(3) - insect and rodent control-openings

2 ptsCorrected: NoRepeat: No

Observed access door to roof on second floor not sealed to prevent entrance of pests

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed hole in wall in second floor storage room. PIC will have hole repaired

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

Observed a gap where the wall and flooring meet in room 320. PIC will have opening repaired