May 19, 2026
Permit/Opening
19 - adequate turnover rate
13-190(a): Equipment shall be operated to obtain 1 turnover every 6 hours. The minimum flow meter reading to achieve the required turnover rate for this pool is 156 gpm. Observed flow meter at 90 gpm.