Dec 17, 2025
Routine
3 - hot/cold running water under pressure in all required locations of tourist accommodation
Regulation: 511-6-2-.07(2) - hot water supply
Observed no hot water in rooms 228,222 and 127. CA: Hot running water under pressure shall be provided to all equipment that uses water
8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot
Regulation: 511-6-2-.15(5) - heating and fire safety-inspection
Observed no gas-fired equipment inspections. CA: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment
26 - ventilation provided and lighting adequate; guestroom kitchenettes/cooking facilities approved
Regulation: 511-6-2-.14(3) - room ventilation
Observed A/C filters soiled in rooms 228,222,118 and 127. CA: Ventilation shall be provided for all rooms. Where ventilation is provided by means of windows, they shall open directly to the outside air and the openable window area of each room shall be not less than 1/20 of the floor area served. Where ventilation is provided by other means, it shall comply with the requirements of the current International Mechanical Code with Georgia Amendments or future subsequent revisions adopted thereafter to provide comfortable living conditions, remove objectionable odor and fumes, and prevent excessive condensation