Dunwoody, DeKalb County

FLATS AT PERIMETER PLACE ( POOL)

60 PERIMETER CENTER PL NE ATLANTA, GA 30346

Pool
Latest score
94
May 5, 2026
City
Dunwoody
County
DeKalb
Inspections
9

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 5, 2026

Permit/Opening

Score: 943 violations

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4): Each skimmer shall have a properly designed and operating weir. Observed 3 of 5 skimmers without a weir. No IHH at this time.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(c)(3): 2 lavatory with tempered water 70F to 104F shall be provided for each 100 women or men. Observed no hot water in either restroom, however water heaters were present just not functional. No IHH at this time.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-191(4): Pool wastewater shall be directed to a sanitary sewer. Observed minimal water backing up out of backwash drain into pool equipment room. No IHH at this time.

Jun 17, 2025

Permit/Opening

Score: 942 violations

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a): Pool shall run on an adequate turnover rate to achieve a minimum of 4 turnovers per 24 hours.

Observation: observed flow meter at 120 gpm. They have a feature so it should be at minimum 187.5gpm.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(c)(3): The bathroom shall have hot water with range of 70-104 degrees Fahrenheit.

Jun 12, 2025

Permit/Opening

Score: 824 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1): Chlorine levels shall be maintained within a range of 3-10ppm.

Observation: Chlorine initial reading was 10.73. The second reading is 11.73. The third reading is 11.41.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m): Rules must contain at a minimum the 12 statements.

Observation: The sign is missing these rules-- Bathers with opens wounds, skin conditions or any communicable condition not allowed; No spitting, spouting, blowing nose, or any bodily excretion allowed; No running, rough or boisterous play allowed.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(c)(3): The bathrooms shall have tempered water with range of 70-104 degrees Fahrenheit.

Observation: No hot water in bathroom sinks.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(j): The bathrooms shall have trash cans with a lid, and liner.

Observation: The bathrooms have a lined can but no lid.

Jul 22, 2024

Re-inspection

Score: 717 violations

11 - appropriate lifesaving equipment present

15 ptsCorrected: YesRepeat: No

13-202(d) Life saving equipment shall be mounted in a conspicuous place and be readily available for use. Observed that life saving equipment was not mounted in a conspicuous place.

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate gallons per minute. Observed flow meter with bobber piece stuck at the bottom of meter and could not show accurate flow rate.

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4) Each skimmer shall have a properly designed and operating weir or other approved means of skimming effectively. Observed that several skimmers inside pool did not have a weir; two out of the five weirs missing.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: YesRepeat: Yes

13-202(m): Safety rules and regulations shall be easily readable and shall be conspicuously posted in the pool area. Rules must contain at a minimum the twelve statements in pool code. Observed that pool rules signage was down upon arrival.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(k) At all times an adequate amount of liquid soap, toilet paper, and paper towels shall be provided. Observed that during inspection soap was missing from men's restroom and paper towels missing from women's restrooms.

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

13-201(b) Shower with tempered water with a temperature range between 70 and 104 degrees Fahrenheit shall be provided. Observed that deck rinse shower was leaking.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-187(c) Operating permit framed and displayed in public view at all times as close to pool entrance as possible. Observed that pool operating permit was not posted in the pool area.

Jul 9, 2024

Routine

Score: 768 violations

2 - self-closing / self-latching gates

15 ptsCorrected: NoRepeat: No

13-202(a)(2): Entry into pool area shall be at shallow end of the pool through self closing, self latching gate or door. Must be able to self close when opened 4 inches or more as measured from latch to latching mechanism. Observed that pool gate going to restrooms next to deck rinse shower did not self latch.

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(h): Phone number of pool operator, manager, and of health department shall be posted next to phone. Observed that emergency phone contact list needs to be updated.

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1): Free chlorine residual in all parts of pool shall be maintained at no less than 3 ppm and shall not exceed 10 ppm. Observed that pool chlorine test results were at 1.37 ppm.

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4): Each skimmer shall have a properly designed and operating weir or other approved means of skimming effectively. Observed that several skimmers inside pool did not have a weir.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: Yes

13-202(m): Safety rules and regulations shall be easily readable and shall be conspicuously posted in the pool area. Rules must contain at a minimum the twelve statements in pool code. The lettering shall be a minimum of 3/4" except as otherwise noted. Observed that pool rules signage was not placed in location providing clear view and missing several required statements.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-184(e)(5): Imminent health hazard exists if sanitary facilities are not functional or maintained in clean and sanitary condition. Observed that pool restrooms were locked and not in service during inspection.

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

13-201(b): A shower with tempered water with a temperature range between 70 and 104 degrees Fahrenheit shall be provided. Observed that deck rinse shower was not operational.

31 - dressing showers: clean, maintained, hot and cold water available

1 ptsCorrected: NoRepeat: No

13-201(c)(4): If there is a bathhouse: 1 shower with tempered water with a temperature range of 70 to 104 degrees Fahrenheit shall be provided for each 100 men or women. Observed that pool restrooms locked during inspection, dressing showers inaccessible.

May 30, 2024

Permit/Opening

Score: 923 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

13-190(a): The equipment shall be operated continuously on a twenty-four-hour basis to obtain the minimum required number of turnovers per day. Observed-Flow meter indicated equipment operating at a rate that will not achieve the required number of turnovers. Required rate is 125 gpm and meter was observed at 75 gpm.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(b) - (b) warning signs for spas shall be in clear view of the spa and prominently displayed. signs shall state the spa's address, the location of the nearest telephone with references that emergency telephone numbers are posted at the location. these emer

2 ptsCorrected: NoRepeat: No

13-202(m): Safety rules and regulations shall be easily readable and shall be conspicuously posted in the pool area. The lettering shall be a minimum of 3/4" except as otherwise noted. Observed-Safety rules for pool area lacking several required statements

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-201(c)(3): 1 lavatory, with tempered water with a temperature range of 70 to 104 degrees Fahrenheit shall be provided for each 100 men or women. Observed - Women's restroom not functional advising maintenance.

Jul 19, 2023

Permit/Opening

Score: 981 violation

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(c)(3): 1 lavatory with tempered water with a temperature range of 70-104F shall be provided for each 100 men or women. Observed women's sink without hot water

Jul 17, 2023

Permit/Opening

Score: 735 violations

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1): The pool pH shall be maintained between 7.2 - 7.8 at all times. Observed pH at 8.1. Imminent health hazard.

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): An adequately sized flow meter shall be installed on the return line. Observed flow meter with bobber stuck at the bottom and could not show accurate flow rate.

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-189(c)(4): Pool water shall be tested for disinfectant and pH at least 2 times per day. Observed log missing many days of testing and only testing once per day.

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(k): At all times an adequate supply of liquid soap, paper towels, and toilet paper shall be provided. Observed soap dispensers not operational. Advised to provide manual soap dispensers until digital dispensers could be repaired.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i): Each pool facility shall have a departmentally approved Emergency Action Plan with the following sections: Chemical Emergency Evacuation Plan, Emergency Crisis Plan, Water Rescue and Injury Plan, and Drill Procedures for Emergency Situations.

Jun 12, 2023

Permit/Opening

Score: 797 violations

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-189(c)(6): Emergency phone must be operable. Observed emergency phone was not operable. No CPO's number, health department number and management number was posted.

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1): the pool shall be maintained in pH level of 7.2 to 7.8. observed pH level to be higher than the required level.

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: No

13-189 (c)(2): cyanuric acid level shall not exceed 100ppm. observed; cyanuric acid level exceeds 100ppm.

31 - dressing showers: clean, maintained, hot and cold water available

1 ptsCorrected: NoRepeat: No

13-201(c)(4): observed deck shower not to be operational.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i): Emergency action plan must be available. Observed: no emergency action was available.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(k): Each pool shall be supplied with a readily available first aid kit equipped. observed; first aid kit hand handle is broken and needs to replace it.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-198(c): observed leaks in the equipment room. notes to label/ pipping must be identified clearly and mark.