May 23, 2025
Permit/Opening
70 PERIMETER CENTER E ATLANTA, GA 30346
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
13-190(a)The equipment shall be operated continuously on a 24 hour basis to obtain the minimum required number of 4 turnovers per day, or one turnover every 6 hours.
13-184(e)(5) Unsecured handrails considered an imminent health hazard -safety hazard
Routine
13-202(a)(2)Gate/door must have be self-closing, self-latching
13-189(c)(2) Cyanuric acid levels shall not exceed 100ppm
Permit/Opening
13-191(a) All valves and piping in the equipment rooms shall be clearly labeled and water flow direction shall be indicated. Observed line marked as "Vaccuum line" but PIC and CPO company state it was the skimmer line.
13-200(a) Observed two light bulbs not tightly secured to wall. Electrical wiring, fixtures and installation shall conform to state, county and local building code requirements.
Permit/Opening
13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate turn over in gallons per minute. Observed flow meters nit working at time of inspection.
13-196(a)(4) Two of four observed skimmer baskets were in disrepair, needs to be replaced. Each skimmer shall have functional parts for providing effective skimming.