Apr 17, 2026
Permit/Opening
28 - flow meter: appropriate range and location
13-190(a)(7): An adequately sized flow meter shall be used to accurately indicate the circulation rate. Observed a flow meter with maximum sch. 40 GPM reading of 120. The minimum flow meter reading to reach a turnover rate of 4 hours for this pool is 240, making this flow meter inadequately sized.
12 - grab/hand rails, ladders installed and secure
13-184(e)(5): Unsecured hand rails considered a safety hazard. Observed both step railings loose. Pool can be open, no IHH present at this time.
30 - deck/rinse shower maintained
13-201(b): A shower with tempered water between 70F and 104F shall be provided at each entrance to pool area, no more than 25 ft. from entrance.
37 - other violations of the chapter
13-202(i): Pool shall have a departmentally approved Emergency Action Plan(EAP). Observed no EAP at the time of inspection.
37 - other violations of the chapter
13-198(a): Equipment for pool shall be located in a completely enclosed area and the entry door shall be kept locked except for when servicing pool equipment. Observed equipment room area outside with no lock on the entrance and with no roof/enclosure.