19 - adequate turnover rate
Observed calculated turnover rate at 12 hours. Turnover rate should be 6 hours. Need flow rate of at least 165 gpm to achieve a 6 hour turnover rate.
3208 HENDERSON MILL RD ATLANTA, GA 30341
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Observed calculated turnover rate at 12 hours. Turnover rate should be 6 hours. Need flow rate of at least 165 gpm to achieve a 6 hour turnover rate.
Routine
13-202(c): Each pool operator shall maintain and have available data from self-inspected water testing. Record logbook found in the women's restroom had no chemicals recorded since 7/13
13-196(a) Each skimmer shall have a properly designed and operating weir or other departmentally approved means of providing effective skimming. Observed: The skimmer closest to the bathroom has broken weir door and not providing effective skimming, leaves on pool surface.
13-202(i): Each pool facility shall have in place a departmentally approved EAP. Phone numbers of CPO, management, and health department should be posted near emergency phone. Observed: Fulton county phone number was posted. Need to update phone number to Dekalb county's health department
Routine
13-196(a) Each skimmer shall have a properly designed and operating weir or other departmentally approved means of providing effective skimming. Skimmers were dirty and skimmer closest to ladder was not operational
13-201 (c)(4) If there is a shower available, should have tempered water with temperature range between 70F to 104F provided for each 100 men or women. It did not have hot water
Permit/Opening
13-190(a)(7)- Unable to accurately read the flow meter as the bobble was way above the limit (120gpm Sch 40). CA: An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute (GPM). Discussed with CPO that he will have to get a a bigger flow meter
13-201(c)(3)- Observed both men's and women's restrooms without adequate hot water. CA: 1 Lavatory, with tempered water with a temperature range of 70F - 104F shall be provided for each 100 men or women.
Re-inspection
13-201(c)(3): 1 Lavatory for men and for women must have water with a temperature range of 70 degrees F and 104 degrees F. Neither bathroom had hot water. 13-201(k) A minimum of 1 changing table shall be available in both bathrooms. Observations: no changing tables in either bathroom.
Routine
13-189(c)(1): pH should be maintained at between 7.2 and 7.8. Observed: Three tests were conducted, none of which showed a pH above 7.0.
13-202(c): Each pool operator shall maintain and have available data from self-inspected water testing. Record book found in the women's restroom was blank.
13-187(c)a copy of the pool operators permit shall be posted near the operating permit Observation: cpo permit not posted
13-201(c)(3): 1 Lavatory for men and for women must have water with a temperature range of 70 degrees F and 104 degrees F. Neither bathroom had hot water. 13-201(k) A minimum of 1 changing table shall be available in both bathrooms. Observations: no changing tables in either bathroom.
Routine
13-202(c): Each pool operator shall maintain and have available data from self-inspected water testing. Record book found in the women's restroom was blank.
13-201(c)(3): 1 Lavatory for men and for women must have water with a temperature range of 70 degrees F and 104 degrees F. Neither bathroom had hot water. 13-201(k) A minimum of 1 changing table shall be available in both bathrooms. Observations: no changing tables in either bathroom.
13-187(c): Current inspection report shall be displayed in area that can be viewed upon entering pool. Report was in a binder inside the bathroom.
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
At the time of inspection flow meter was not operational.
Regulation: 511-3-5-.19(1)(e ) - (e) hot and cold water under pressure shall be provided in dressing facility showers.
Hot and cold water shall be a minimum of 100F at hand sink in on men and women restrooms. Observed men and women restrooms lacking water temperature of a minimum of 100F. At the time of inspection restroom faucet were operating at low pressure without hot water. Informed property manager to repair to provide hot water.
Routine
13-187(c) - Current inspection report shall be displayed in area that can be viewed upon entering pool. Report was in a binder inside the bathroom.
13-187 (c) - Operating permit must be posted up in clear view. Permit is expired, new one must be posted.
Permit/Opening
Regulation: 511-3-5-.19(1)(e ) - (e) hot and cold water under pressure shall be provided in dressing facility showers.
Hot and cold water shall be a minimum of 100F at hand sink in on men and women restrooms. Observed men and women restrooms lacking water temperature of a minimum of 100F.
Pool shall have a first aid kit to treat a minimum of 15 people. Observed pool lacking first aid kit.