Jul 25, 2025
Re-inspection
17 - skimmers/gutters maintained and operable
skimmers missing weirs and are not pulling
2999 WINDY HILL RD SE MARIETTA, GA 30067-6044
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
skimmers missing weirs and are not pulling
Routine
Emergency phone not operational, unable to make calls, fix ASAP
skimmers missing weirs and are not pulling
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
pH observed less than 7.0; must be between 7.2 - 7.8
Regulation: 511-3-5-.18(10)(b) - (b) a minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inch
Obtain life ring rope
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed the flow meter stuck. CA 511-3-5-.07(4)(b) - (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed the double grab bars at the 3Ft mark and the single handle at the entrance to the pool loose. Must tighten the handles. CA 511-3-5-.06(3)(f)1. - 1. Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Permit/Opening
"No Diving" signage needed on deck level edge at 5ft dept marker
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
'No diving" signage needed on deck level edge at 5ft dept marker
Relocate "Pool Risks" sign to pool entry Provide fecal contamination and disinfection instructions in pumproom
Routine