WESTIN ATLANTA AIRPORT HOTEL (Indoor)

4736 BEST RD ATLANTA, GA 30337

Pool
Latest score
100
May 19, 2026
City
College Park
County
Clayton
Inspections
8

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 19, 2026

Routine

Score: 1000 violations
No violations recorded for this inspection.

May 22, 2025

Permit/Opening

Score: 991 violation

24 - piping identified and marked

Regulation: 511-3-5-.08(6) - (6) all piping shall be marked with directional arrows as necessary to determine flow direction. all piping in the equipment room shall be permanently identified by its use and the pool and or aquatic feature it serves.

1 ptsCorrected: YesRepeat: No

Observed directional flow not marked. COS- directional flow marked

Dec 9, 2024

Routine

Score: 1000 violations
No violations recorded for this inspection.

Jul 2, 2024

Re-inspection

Score: 832 violations

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: YesRepeat: No

Observed pH reading of 7.0. Advised PIC chemical values shall be at pH 7.2 7.4-7.6 7.8. COS: Had PIC adjust pH to adequate range.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed no, 'No Diving' tiling at depths of 5ft or less. Advised PIC 'No Diving' tiling shall be placed at depths of 5ft or less, in 4-inch height lettering.

Jun 17, 2024

Re-inspection

Score: 833 violations

4 - water clarity: main drains clearly visible

Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e

15 ptsCorrected: NoRepeat: No

Observed cloudy water could not see main drain. Advised PIC water shall be clear, main drain shall be clearly visible.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed pH of 8.0. Advised PIC pH shall be between 7.2 to 7.8.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed no, 'No Diving' tiling at depths of 5ft or less. Advised PIC 'No Diving' tiling shall be placed at depths of 5ft or less, in 4-inch height lettering.

Jun 10, 2024

Permit/Opening

Score: 826 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Observed inadequate turnover rate greater than 6 hours. Advised PIC pool equipment shall be able to turn adequately with its given pool volume.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed flow meter reading not accurate. Advised PIC that flow meter shall be designed to give an accurate reading.

15 - depth and no diving markers, step marking; installed and contrasting

Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.

4 ptsCorrected: NoRepeat: No

Observed No 'NO DIVING' tile markers permanently installed on the pool deck for areas 5 ft or less. Advised PIC 'NO DIVING" tile markers shall be permanently installed in at least 4-inch lettering and numbers in contrasting color.

12 - grab/hand rails, ladders installed and secure

Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

2 ptsCorrected: NoRepeat: No

Observed multiple loose grabrails. Advised CPO that grabrails shall be tighten in order to prevent movement without the use of a tool.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed No "NO LIFEGUARD ON DUTY. SUPERVISE CHILDREN CLOSELY." signage posted. Advised PIC that facility shall have "NO LIFEGUARD ON DUTY. SUPERVISE CHILDEN CLOSEY" signage posted on the pool deck area.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: No

Observed no theoretical peak occupancy sing or no hours of operation sign posted near the pool entrance. Advised PIC that a theoretical peak occupancy sign and hours of operation sign shall be posted near the entrance of the pool .

Dec 13, 2023

Routine

Score: 991 violation

34 - inspection report placed in public view

Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

1 ptsCorrected: NoRepeat: No

Upon arrival, observed 2022 inspection report posted in public view. Advised PIC that the most recent inspection report shall be posted at all times.

Jun 22, 2023

Permit/Opening

Score: 981 violation

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed indoor pool w/o No Diving words on tile of deck. Advised to obtain