Jun 8, 2026
Permit/Opening
2 - self-closing / self-latching gates
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
Observed entry gate of pool not self-latch at close distances. Gates shall be operable with self-latch self-closing mechanism. COS: CPO corrected, gate able to self-close, self-latch.
19 - adequate turnover rate
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed inadequate turnover at time of inspection above 6-hours (80 GPM). Pool shall be able to turn over pool volume adequately.
12 - grab/hand rails, ladders installed and secure
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed no end caps at grab rail. Handrails, shall be installed cannot be removed.