Jun 3, 2026
Permit/Opening
704 BARTOW ST WALESKA, GA 30183
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter stuck - Repair
Deck shower not operational-repair
Water fountain out of order- Repair
Routine
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
Observed gate not self closing. Must fix.
Regulation: .17((1)(c) - proper disinfectant level
Observed Cl- at 0 ppm. Must be between 2-10 ppm.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meters appear to not be working, was unable to read turnover rate. Must fix.
Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.
Observed no paper towels in women's restroom. Must supply with paper towels.
Re-inspection
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed turn over rate at 200gpm. Must be atleast 345gpm.
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH lower than 7.0. Must be brought to between 7.2 and 7.8.
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed turn over rate at 200gpm. Must be atleast 345gpm.
Re-inspection
Routine
Observed chlorine at .5 ppm. Must be brought to safe operating level.
pH lower than 7.0. Must be brought to between 7.2 and 7.8.
Permit/Opening
Re-inspection
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH is greater than 8.0
Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.
Deck shower not working.