Holly Springs, Cherokee County

One Life Fitness

4512 HOLLY SPRINGS PKWY CANTON, GA 30115

Pool
Latest score
100
Aug 28, 2025
City
Holly Springs
County
Cherokee
Inspections
14

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Aug 28, 2025

Routine

Score: 1000 violations
No violations recorded for this inspection.

Aug 25, 2025

Routine

Score: 961 violation

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Make sure the weirs are fixed correctly.

Jun 17, 2025

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

Jun 2, 2025

Routine

Score: 763 violations

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Emergency phone not working. 511-3-5-.18(10)(c ) - (c) An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim (c) An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times. The emergency phone shall be capable of connecting to 911 and electronically transferring an automatic number identification and automatic locator identification of the pool emergency phone to the public safety answering point, if available. A 911 sign or the names and phone numbers of the nearest available police, fire, ambulance service or rescue unit shall be posted nearby.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: YesRepeat: No

Chlorine and pH must be tested twice a day and the logs must be maintained onsite.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.

4 ptsCorrected: NoRepeat: No

Must install effluent pressure gauge on the return line.

Oct 31, 2024

Re-inspection

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Turn over rate is at 150gpm. Must be 180gpm.

Oct 31, 2024

Routine

Score: 851 violation

6 - proper disinfectant level

Regulation: .17(1)(a)(b) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed chlorine at 0ppm. Mut be between 2 and 10ppm.

Oct 8, 2024

Routine

Score: 951 violation

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Chlorine and pH must be tested twice a day and the logs must be maintained onsite.

Oct 4, 2024

Routine

Score: 981 violation

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: No

Must post peak occupancy in 4 inch letters.

Aug 7, 2024

Routine

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Flow meter reading 140 at time of inspection. Increase flow rate to at least 180 to meet turnover requirements.

May 30, 2024

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 28, 2024

Routine

Score: 851 violation

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Emergency phone not working.

Jun 21, 2023

Routine

Score: 1000 violations
No violations recorded for this inspection.

Jun 2, 2023

Routine

Score: 1000 violations
No violations recorded for this inspection.

May 25, 2023

Routine

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

OBSERVED TURN OVER RATE BEING LOWER THAN THE REQUIRED RATE. MUST HAVE TURN OVER RATE AT REQUIRED AMOUNT.