Apr 29, 2026
Permit/Opening
37 - other violations of the chapter
Observed no baby changing stations. Baby changing stations must be provided in both bathrooms
37 - other violations of the chapter
Must fix the water fountain before opening the pool.
1011 SMITHWYCK DR CANTON, GA 30115
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Observed no baby changing stations. Baby changing stations must be provided in both bathrooms
Must fix the water fountain before opening the pool.
Re-inspection
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed the cyanuric acid (CYA) level around 100 ppm. Corrective action: lower CYA level to 90 maximum, ideal range is 30-50 ppm.
511-3-5-.17(4) - (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or br (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or brominated pools and spas.
Re-inspection
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
Front gate is not self-closing/self-latching. Must fix.
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone is not working. There is no dial tone. Must fix.
Regulation: .17(1)(a)(b) - proper disinfectant level
Free chlorine is at 19.5 ppm. Must be between 2-10ppm.
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Flow meter is reading around 60 gpm. The turnover rate for pool is 76 gpm.
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Observed no logs for daily chemical testing onsite.
Regulation: 511-3-5-.22(6) - (6) written documentation of the operator’s visits must be available at the pool facility. at a minimum, the written record must indicate the condition of the following items:
Observed no CPO logs onsite as required. Logs on clipboard were all blank.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Hand rails are very loose. Must tighten.
Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.
Observed no soap in men’s restroom. Must supply with soap.
Routine
Regulation: .17((1)(c) - proper disinfectant level
Free chlorine measured at 24.5 ppm. Must be between 2.0–10.0 ppm when using stabilized chlorine. Immediate closure required per DPH Rule 511-3-5-.17(1)(c).
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
No documentation was available. Trained operator must document visits and perform a minimum of two visits per week per DPH Rule
Observed CPO certificate not available on site. Must keep copy of certificate on site.
Observed no baby changing stations. Baby changing stations must be provided in both bathrooms
Does not say pool phone. 911 operator stated the facility will need to get in contact with VOIP to get it sorted out.
Re-inspection
Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.
Observed CPO certificate not available on site. Must keep copy of certificate on site.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed hand rail above stairs very loose. Must fix.
Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.
Observed no soap in men’s restroom. Must supply with soap.
Re-inspection
There is a sizeable opening in fence. Opening is large enough for a small child to squeeze through. There should be no openings in fence.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Hand rail on shallow end is extremely loose. Must tighten.
Regulation: 511-3-5-.19(2)(e ) - (e) soap dispensers for providing either liquid or powdered soap shall be provided at each lavatory. the dispenser shall be of all metal or plastic. no glass shall be permitted in these units.
There is no soap in men's rest room. Must supply.
Permit/Opening
Regulation: 511-3-5-.18(10)(b) - (b) a minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inch
Observed no life saving buoy. Must have a minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inches or a similar flotation device which is U.S. Coast Guard approved.
Routine
Permit/Opening
Re-inspection
Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
Inspection report must be posted in public view.
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone is not working. There is a dial tone but when you enter a number, it doesn't go through.