May 21, 2026
Routine
102 WALDEN CROSSING DR CANTON, GA 30115
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
Re-inspection
Observed a turnover rate of 80 gpm. The required turnover rate for this pool is 114 gpm. Suggest backwashing.
No safety self-inspection logs documented since June 30. Daily inspections must be completed and recorded by the trained operator or responsible person per DPH Rule
Routine
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH measured above 8.0 during inspection. Must be maintained between 7.2–7.8 per DPH Rule 511-3-5-.17(2). Immediate closure required.
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed a turnover rate of 80 gpm. The required turnover rate for this pool is 114 gpm. Suggest backwashing.
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
No safety self-inspection logs documented since June 30. Daily inspections must be completed and recorded by the trained operator or responsible person per DPH Rule
Regulation: 511-3-5-.11(3)(g) - (g) the skimmer equalizer lines shall be protected by an approved cover/grated with a flow rating equal the maximum system flow divided by the number of skimmers in the system or the maximum flow rating of the skimmer, whichever is greater.
Skimmer baskets filled with debris at time of inspection. Skimmers must be maintained to ensure proper flow and protection of equalizer lines per DPH Rule
Regulation: 511-3-5-.22(5) - (5) the trained operator must perform a minimum of two visits weekly and be able to provide assistance whenever needed.
Certified pool operator stated daily checks are performed, but no documentation was available. Trained operator must document visits and perform a minimum of two visits per week per DPH Rule
Mildew on side of pool
Permit/Opening
Observed a turnover rate of 80 gpm. The required turnover rate for this pool is 114 gpm. Suggest backwashing.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed skimmers missing weirs. Must install weirs.
Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.
Observed CPO certificate not readily available. Must keep certificate on site and easily accessible. Must email Health Authority copy.
Routine
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed a turnover rate of 60 gpm. The required turnover rate for this pool is 114 gpm.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed some skimmers missing weirs. All skimmers must have weirs.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed a concentration of 100 ppm cyanuric acid. The maximum concentration is 90 ppm.
Routine
Re-inspection
Routine
Regulation: .17((1)(c) - proper disinfectant level
Free chlorine is at 0.5 ppm. Must be between 2-10 ppm.