May 21, 2026
Permit/Opening
5 - emergency phone operational and accessible
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone is showing up as wireless on 911 call. Address is not updated on the system.
(c) An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times. The emergency phone shall be capable of connecting to 911 and electronically transferring an automatic number identification and automatic locator identification of the pool emergency phone to the public safety answering point, if available. A 911 sign or the names and phone numbers of the nearest available police, fire, ambulance service or rescue unit shall be posted nearby.
6 - proper disinfectant level
Free chlorine is less than 2 ppm.
RCA: Ensure free chlorine is maintained between 2-10 ppm at all times.
28 - flow meter: appropriate range and location
Flow meter is not operational at time of inspection.
RCA: (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
37 - other violations of the chapter
Observed calcium hardness at 58 ppm.
RCA: Ensure calcium hardness is maintained between 150 and 1000 ppm at all times.
37 - other violations of the chapter
Observed calcium hardness at 58 ppm.
RCA: Ensure calcium hardness is maintained between 150 and 1000 ppm at all times.