Feb 10, 2026
Routine
8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot
Regulation: 511-6-2-.15(5) - heating and fire safety-inspection
Observed the facility to not have the annual gas fired equipment inspection.
RCA: 511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency
28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered
Regulation: 511-6-2-.14(6) - bed, bedding, and linens
Observed pillow staining in rooms 123, 161, 217, 230, 241, and 262. Observed mattress staining in rooms 161, 241, and 262.
Rule: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin
16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair
Regulation: 511-6-2-.08(6) - artificial light
Observed the bathroom/sink lights to not be working in rooms 142 and 230.
Rule: Toilet rooms, lavatories and bathing facilities shall be provided with soap, artificial light, and hot and cold water under pressure
17 - proper ventilation; no sign of mold, mildew, odors or moisture
Regulation: 511-6-2-.08(5) - toilet and bathing ventilation
Observed the bathroom vents to not be working and slight mold like debris on the bathroom ceiling in rooms 123, 230, and 262.
Rule: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems