Kingsland, Camden County

Marriott Fairfield Inn & Suites

1319 KING AVE KINGSLAND, GA 31548

Pool
Latest score
100
Mar 17, 2026
City
Kingsland
County
Camden
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 17, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Nov 5, 2025

Routine

Score: 912 violations

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

At time of inspection, the flow meter appears to be stuck. Repair/replace the flow meter.

20 - return inlets maintained

Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.

4 ptsCorrected: NoRepeat: No

At time of inspection, the return inlet covers are missing from the spa. Replace return inlet covers.

Jun 12, 2025

Re-inspection

Score: 951 violation

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: Yes

At time of follow-up inspection, the flow meter is still not functioning. CPO will repair/replace the flow meter.

Jun 6, 2025

Permit/Opening

Score: 755 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

At time of inspection, free chlorine (FCL) level registered at 10.55 ppm (FCL for spas must be within 3.00 - 10.00 ppm). CPO is adding more water, as the water level was a little low when he arrived.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: NoRepeat: No

At time of inspection, the pH registered at 8.3 (pH must be within 7.2 - 7.8). CPO added muriatic acid to the spa, to lower the pH to within acceptable range.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

At time of inspection, the flow meter is not functioning. Repair/replace flow meter.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.

4 ptsCorrected: NoRepeat: No

At time of inspection, the pressure gauge on the filter is broken. Replace pressure gauge.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

At time of inspection, the total alkalinity registered at 245 ppm (alkalinity must be within 60 - 180 ppm). CPO added muriatic acid to the spa, to lower the pH and the total alkalinity.

Nov 19, 2024

Re-inspection

Score: 812 violations

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: Yes

At time of inspection, the pH is still high (8.2, at time of inspection; pH must be 7.2-7.8). PIC will have the CPO adjust. Pool/spa area already closed with door locked (and with "closed" signage), at time of inspection. Spa must remain closed, until pH is within range and spa passes re-inspection.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.

4 ptsCorrected: NoRepeat: Yes

At time of inspection, the pressure gauge is still not functioning. The facility is still working towards replacing the pressure gauge.

Nov 15, 2024

Permit/Opening

Score: 813 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

At time of inspection, the disinfectant level is below the minimum level required (spa disinfectant level must be at least 3.00 ppm). CPO will adjust. Pool/spa area already closed with door locked (and with "closed" signage), at time of inspection. Spa must remain closed, until chlorine level is within range and spa passes re-inspection.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: NoRepeat: No

At time of inspection, the pH is 8.1 (pH must be 7.2-7.8). CPO will adjust. Pool/spa area already closed with door locked (and with "closed" signage), at time of inspection. Spa must remain closed, until pH is within range and spa passes re-inspection.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.

4 ptsCorrected: NoRepeat: No

At time of inspection, the pressure gauge is not functioning. Facility will replace the gauge.